Pellet stove service can be dangerous and complicated, use this information safely
1) TURN ON THERMOSTAT CIRCUIT AND MAKE SURE THAT THE CALL LIGHT IS ON
2) CHECK FOR POWER AT THE VACUUM SWITCH:
A. IF NO POWER FROM RED WIRE—–CHECK CONTROL BOX OR WIRE HARNESS
B. POWER ON RED BUT NO POWER ON ORANGE—–CHECK VACUUM SWITCH OR VENT SYSTEM
3) CHECK FOR POWER AT THE ORANGE WIRE ON THE #2 SNAP DISC:
A. IF NO POWER FROM ORANGE WIRE—-CHECK WIRE HARNESS OR RESET THE SNAP DISC
B. IF POWER IS PRESENT—–REPLACE FEED MOTOR OR CHECK CONNECTOR PIN OR CAPACITOR
2) TURN ON THE EXHAUST BLOWER SWITCH. (THIS WILL PULL THE VACUUM SWITCH IN)
3) TURN ON THE THERMOSTAT (THE THERMOSTAT INDICATOR LIGHT SHOULD COME ON)
4) TURN ON THE FEED MOTOR SWITCH:
IF THE FEED DOESN’T COME ON: BAD FEED MOTOR, VACUUM SWITCH, OR #2 SNAP DISC
IF THE FEED COMES ON: REPLACE CONTROL BOX
NOTE: THE NEW STYLE FEED MOTOR WILL NEED THE CAPACITOR JUMPER ADDED TO THE ADAPTER.